arXiv · 1602.05632
Distributed Monitoring of Voltage Collapse Sensitivity Indices
Abstract
The assessment of voltage stability margins is a promising direction for wide-area monitoring systems. Accurate monitoring architectures for long-term voltage instability are typically centralized and lack scalability, while completely decentralized approaches relying on local measurements tend towards inaccuracy. Here we present distributed linear algorithms for the online computation of voltage collapse sensitivity indices. The computations are collectively performed by processors embedded at each bus in the smart grid, using synchronized phasor measurements and communication of voltage phasors between neighboring buses. Our algorithms provably converge to the proper index values, as would be calculated using centralized information, but but do not require any central decision maker for coordination. Modifications of the algorithms to account for generator reactive power limits are discussed. We illustrate the effectiveness of our designs with a case study of the New England 39 bus system.
Explore related subjects
Keep this discovery
John W. Simpson-Porco, Francesco Bullo. 2016-02-18. Distributed Monitoring of Voltage Collapse Sensitivity Indices. https://doi.org/10.1109/tsg.2016.2533319
Cite the original work for its findings. Save a collection to share your selection of sources.