arXiv · 1705.01981
Multi-Stage Holomorphic Embedding Method for Calculating the Power-Voltage Curve
Abstract
The recently proposed non-iterative load flow method, called the holomorphic embedding method, may encounter the precision issue, i.e. nontrivial round-off errors caused by the limit of digits used in computation when calculating the power-voltage (P-V) curve for a heavily loaded power system. This letter proposes a multi-stage scheme to solve such a precision issue and calculate an accurate P-V curve. The scheme is verified on the New Eng-land 39-bus power system and benchmarked with the result from the traditional continuation power flow method.
Explore related subjects
Keep this discovery
Bin Wang, Chengxi Liu, Kai Sun. 2017-05-04. Multi-Stage Holomorphic Embedding Method for Calculating the Power-Voltage Curve. https://arxiv.org/abs/1705.01981