arXiv · 1705.09849
Power System Supplementary Damping Controllers in the Presence of Saturation
Abstract
This paper presents the analysis and a method to design supplementary damping controllers (SDCs) for synchronous generators considering the effects of saturation limits. Usually such saturations of control signals are imposed in order to enforce practical limitations such as component ratings. However, to guarantee the stability in the presence of saturation limits, the state trajectories must remain inside the domain of attraction (DA). In this paper, the domain of attraction of a single-machine infinite-bus (SMIB) power system with saturation nonlinearity is estimated and compared with the exact description of the null controllable region. Then, state-feedback controllers are designed to enlarge the DA. Our analysis shows that nonlinear effects of saturation should be considered to guarantee stability and satisfactory performance. Simulation results on a detailed nonlinear model of a synchronous generator indicate that the DA enlarges with the proposed controller. The results also indicate that Critical Clearing Time (CCT) and damping of the system with saturation can be improved by the proposed method.
Explore related subjects
Keep this discovery
M. Ehsan Raoufat, Kevin Tomsovic, Seddik M. Djouadi. 2017-05-27. Power System Supplementary Damping Controllers in the Presence of Saturation. https://arxiv.org/abs/1705.09849
Cite the original work for its findings. Save a collection to share your selection of sources.