arXiv · 1708.06424
Online Coherence Identification Using Dynamic Time Warping for Controlled Islanding
Abstract
Controlled islanding is considered to be the last countermeasure to prevent system-wide blackouts in case of cascading failures. It splits the system into self-sustained islands to maintain transient stability at the expense of possible loss of load. Generator coherence identification is critical to controlled islanding scheme as it helps identify the optimal cut-set to maintain system transient stability. This paper presents a novel approach for online generator coherency identification using phasor measurement unit (PMU) data and dynamic time warping (DTW). Results from the coherence identification are used to further cluster non-generator buses using spectral clustering with the objective of minimizing power flow disruption. The proposed approach is validated and compared to existing methods on the IEEE 39-bus system, through which its advantages are demonstrated.
Explore related subjects
Keep this discovery
Hasan Ul Banna, Zhe Yu, Di Shi, Zhiwei Wang, Dawei Su, Chunlei Xu, Sarika Solanki, Jignesh Solanki. 2017-08-21. Online Coherence Identification Using Dynamic Time Warping for Controlled Islanding. https://arxiv.org/abs/1708.06424
Cite the original work for its findings. Save a collection to share your selection of sources.