Abstract
Transformers and transmission lines are critical components of a grid network. This paper analyzes the statistical properties of the electrical parameters of transmission branches and especially examines their interdependence on the voltage levels. Some interesting findings include: (a) with appropriate conversion of MVA rating, a transformers per unit reactance exhibits consistent statistical pattern independent of voltage levels and capacity; (b) the distributed reactance (ohms/km) of transmission lines also has some consistent patterns regardless of voltage levels; (c) other parameters such as the branch resistance, the MVA ratings, the transmission line length, etc, manifest strong interdependence on the voltage levels which can be approximated by a power function with different power constants. The results will be useful in both creation of synthetic power grid test cases and validation of existing grid models.
Explore related subjects
Keep this discovery
Mir Hadi Athari, Zhifang Wang. 2017-09-15. Interdependence of Transmission Branch Parameters on the Voltage Levels. https://arxiv.org/abs/1709.06930
Cite the original work for its findings. Save a collection to share your selection of sources.