arXiv · 2211.02776
Detection of High Impedance Faults in Microgrids using Machine Learning
Abstract
This article presents differential protection of the distribution line connecting a wind farm in a microgrid. Machine Learning (ML) based models are built using differential features extracted from currents at both ends of the line to assist in relaying decisions. Wavelet coefficients obtained after feature selection from an extensive list of features are used to train the classifiers. Internal faults are distinguished from external faults with CT saturation. The internal faults include the high impedance faults (HIFs) which have very low currents and test the dependability of the conventional relays. The faults are simulated in a 5-bus system in PSCAD/EMTDC. The results show that ML-based models can effectively distinguish faults and other transients and help maintain security and dependability of the microgrid operation.
Explore related subjects
Keep this discovery
Pallav Kumar Bera, Vajendra Kumar, Samita Rani Pani, Vivek Bargate. 2022-11-04. Detection of High Impedance Faults in Microgrids using Machine Learning. https://doi.org/10.1109/igessc55810.2022.9955330
Cite the original work for its findings. Save a collection to share your selection of sources.