arXiv · 2511.02497
Decentralized Approach to Detect and Eliminate Flapping Phenomena due to Flexible Resources
Abstract
This paper presents a decentralized methodology for detecting and mitigating flapping phenomena in power systems, primarily caused by the operation of discrete devices. The proposed approach applies moving-window autocorrelation to local measurements, enabling each device to autonomously identify sustained oscillations. Upon detection, a probabilistic, device-specific mitigation strategy is executed. Flexible demand resources (DFRs), under-load tap changers (ULTCs), and automatic voltage regulators (AVRs) are utilised to illustrate the performance of the proposed approach to both discrete and continuous-operation devices. Results show that the proposed method is robust and properly distinguishes damped oscillations from persistent flapping, allowing devices to independently recognize problematic operating scenarios and implement corrective actions accordingly.
Explore related subjects
Keep this discovery
Angel Vaca, Federico Milano. 2025-11-04. Decentralized Approach to Detect and Eliminate Flapping Phenomena due to Flexible Resources. https://arxiv.org/abs/2511.02497
Cite the original work for its findings. Save a collection to share your selection of sources.