Continuous reset element: Transient and steady-state analysis for precision motion systems
Abstract
This paper addresses the main goal of using reset control in precision motion control systems, breaking of the well-known "Waterbed effect". A new architecture for reset elements will be introduced which has a continuous output signal as opposed to conventional reset elements. A steady-state precision study is presented, showing the steady-state precision is preserved while the peak of sensitivity is reduced. The architecture is then used for a "Constant in Gain Lead in Phase" (CgLp) element and a numerical analysis on transient response shows a significant improvement in transient response. It is shown that by following the presented guideline for tuning, settling time can be reduced and at the same time a non-overshoot step response can be achieved. A practical example is presented to verify the results and also to show that the proposed element can achieve a complex-order behaviour.