Ultrafast Grid Impedance Identification in $dq$-Asymmetric Three-Phase Power Systems
Abstract
We propose a non-parametric frequency-domain method to identify small-signal $dq$-asymmetric grid impedances, over a wide frequency band, using grid-connected converters. Existing identification methods are faced with significant trade-offs: e.g., passive approaches rely on ambient harmonics and rare grid events and thus can only provide estimates at a few frequencies, while many active approaches that intentionally perturb grid operation require long time series measurement and specialized equipment. Although active time-domain methods reduce the measurement time, they either make crude simplifying assumptions or require laborious model order tuning. Our approach effectively addresses these challenges: it does not require specialized excitation signals or hardware and achieves ultrafast ($<1$ s) identification, drastically reducing measurement time. Being non-parametric, our approach also makes no assumptions on the grid structure. A detailed electromagnetic transient simulation is used to validate the method and demonstrate its clear superiority over existing alternatives.
Explore related subjects
Keep this discovery
Mohamed Abdalmoaty, Verena Häberle, Xiuqiang He, Florian Dörfler. 2025-10-14. Ultrafast Grid Impedance Identification in $dq$-Asymmetric Three-Phase Power Systems. https://arxiv.org/abs/2510.12338
Cite the original work for its findings. Save a collection to share your selection of sources.