This paper presents a frequency-domain, impedance-based sensitivity methodology for stability assessment and enhancement of line-commutated converter HVDC (LCC-HVDC) links operating under weak-grid conditions. The methodology integrates frequency-domain identification tailored for black-box systems, the Generalized Nyquist Criterion (GNC) for multivariable stability assessment, and modal impedance decomposition with participation-factor analysis to locate and interpret interaction mechanisms. The approach is validated against a detailed linearized state-space model and nonlinear EMT simulations of an LCC-HVDC benchmark. A sensitivity study varying the grid short-circuit ratio (SCR) reveals a stability limit for the standalone LCC-HVDC link and demonstrates that the integration of a grid-forming voltage source converter (GFM-VSC) substantially increases the stability margin.
Explore related subjects
Keep this discovery
Luis A. Garcia-Reyes, Anup Joshi, Javier Renedo, Macarena Martin-Almenta, Oriol Gomis-Bellmunt, Eduardo Prieto-Araujo, Vinicius A. Lacerda, Xavier Guillaud. 2026-09-09. Impedance-Based Sensitivity Analysis for Stability Enhancement of LCC-HVDC Links Connected to Weak Grids Using Grid-Forming Converters. https://arxiv.org/abs/2609.10774